来宝网Logo

热门词:生物显微镜 水质分析仪 微波消解 荧光定量PCR 电化学工作站 生物安全柜

现在位置首页>自动化仪器仪表>传感器/变送器>传感器/变送器> IP211-X15-ISF_IP211-X27-ISF_IP211-X15-ISC电动气动传感器OM

商品编号:74613
分享

IP211-X15-ISF_IP211-X27-ISF_IP211-X15-ISC电动气动传感器OM

价    格:询价

产    地:美国更新时间:2019/9/11 7:42:53

品    牌:欧米茄型    号:IP211-X15-ISF

状    态:正常点击量:25

15221105376
联系我时,请说明是在来宝网上看到的,谢谢!

上海茂培电子科技有限公司

联 系 人:范先生

电     话:15221105376

传     真:

等     级: (第 4年)

性     质:贸易型,

联系我时请说在来宝网上看到的,谢谢!




IP211-X15-ISF_IP211-X27-ISF_IP211-X15-ISC电动气动传感器OMEGA

低成本


内置增压器


小尺寸


场可逆


低耗气量


以任何角度安装


方便的外部跨度和零位调整


(防爆型除外)


宽供气压力范围


供气压力敏感度低


回路供电



产品参数

IP211-X15-ISF_IP211-X27-ISF_IP211-X15-ISC电动气动传感器OMEGA

Low Cost

Built-in Volume Booster

Small Size

Field Reversible

Low Air Consumption

Mounts at Any Angle

Convenient External Span and Zero Adjustment 

(Except for Explosion Proof Models)

Wide Supply Pressure Range

Low Supply Pressure Sensitivity

Loop Powered


The IP211/EP211 Series transducer is an electropneumatic device that reduces a supply pressure to a regulated output pressure directly proportional to an electrical input signal. The 211 Series accepts a wide range of supply pressures, ranging from a minimum of 3 psig (0.2 BAR) above the maximum output up to 100 psig (6.9 BAR). An integral pneumatic volume booster is included in the design to provide high flow capacity (up to 12 SCFM). Model selection includes General Purpose, FM Intrinsically Safe, and CSA Intrinsically Safe.


Mounting

These transducers can be pipe, panel, or bracket mounted in any position. Positions other than verticle will require recalibration of the zero adjustment. For maximum output stability the transducers should be mounted in a vibration free location or such that vibration is isolated in the X and Z axis.


Field Reversible

All transducers are calibrated at the factory for direct acting operation but may be used in the reverse acting mode by reversing the polarity of the signal leads and recalibrating. When recalibrated for reverse acting applications, the transducers provide a minimum of their full rated output pressure (i.e.15, 27, or 30 psig) upon input signal failure.



产品介绍

IP211-X15-ISF_IP211-X27-ISF_IP211-X15-ISC电动气动传感器OMEGA

安装


这些传感器可以安装在任何位置的管道、面板或支架上。垂直以外的位置需要重新校准零点调整。为了获得最大的输出稳定性,传感器应安装在无振动的位置,或在X和Z轴上隔离振动。




场可逆


所有传感器都在工厂进行了直接作用操作的校准,但可以通过颠倒信号线的极性和重新校准在反向作用模式下使用。当为反向作用应用重新校准时,传感器在输入信号故障时提供最小的全额定输出压力(即15、27或30磅/平方英寸)。